SVS-L 2P Series

Servo Electronic
Voltage Stabilisers & Power Line Conditioners
Two / Split Single Phase
5 to 150 kVA

SVS Series - Two / Split Single-Phase
Servo Electronic AC Voltage Stabilizers
5 to 150kVA

Cost efficient voltage stabilization for US style Two-Phase / Split Single-Phase Output Electricity Distribution Systems commonly found in Residential & Light Commercial Buildings.

Now remastered to meet the demands of today’s modern age, our latest generation SVS-L-2P Series offerings include as standard many advanced protection features – usually only available from others as additional expensive add-on options!

Models are offered in 13 different power ratings from 5 to 150 kVA.

To learn more about the range of  Two Phase / Split Single-Phase SVS Voltage Stabilisers and Power Conditioners available from Sinalda UK, please check out the following listings, or download the brochure below:

SINALDA

Standard Features include:

Automatically Controlled Voltage Stabilization / Regulation
Servo Electronic Design – Low Maintenance
Wide Permissible Input Voltage Window (up to ±30%)
TVSS – Transient Voltage Surge & Spike Suppression Protection
Inbuilt High Overload Capability
Over and Under Voltage Protection
Comprehensive Digital Front Panel with
– Output Voltage Metering
– Output Current Metering
– Status Indication
Automatic Restart on Mains Failure
Re-start Time Delay (Presettable)
Start-Up Load Protection
Class II Lightning Surge Arrestors
Electronic Controls Bypass Switch
Freestanding IP20 Indoor Enclosure
Hard Wire Input & Output
Built to comply with leading International Standards
Supplied with a 3 Year / 36 Months Warranty


Optional Features
available include:

Outdoor IP54 Enclosure (-IP54)
Stabiliser presented in endurable IP54 (BS / EN 60529) / NEMA 3 free-standing steel cubicles suitable for external use, or more challenging internal environments
Input Isolating Transformer (-PC)
Through the integration of a shielded isolation transformer, provides enhanced spike & electrical noise (Common Mode: 120db @ 100khz & Normal Mode Noise: 60db @ 100khz) suppression and neutral ground bonding. Delivers what is commonly referred to as a ‘CLEAN’ supply
Full Manual Maintenance Bypass (-MBS)
While many Customers, following traditional wisdom, prefer to install a bypass facility that is external to the Stabilizer/Conditioner, where requested models can be fitted with an integrated traditional ‘Break Before Make’ bypass facility. This feature is handy when performing remedial works or deep maintenance on the system.
AquaStop (-AS)
PCB protective coating offering protection against damp and moisture ingress 
Digital Power Metering (-DPM)
Microprocessor-based output digital power metering, with event logging – monitoring V, A, W, VAR, PF, W Hrs & VAR Hrs and the offering  RS-485, Modbus RTU, Modbus ASCII, Jbus Protocol interface
Alternative Paint Colour (-RAL)
Alternative Paint Colour Finish – customer to specify
Output Circuit Breaker (-OCB)
Replacement of the Output Contactor with an Output Circuit Breaker
UL Recognised Component (-URC)
For 
applications where UL compliance is required, the Stabilizer / Conditioner can be supplied with UL approved Input Breakers and Output Contactors / Breakers, so that the client can obtain on-site UL approval of the installation

SELECT | Permissible Input Voltage Window Options (S*):

Swing OptionsNominal VoltageMax Model Rating
220V230V240V
S15±15%187 to 253V196 to 265V204 to 276V150 kVA
S20±20%176 to 264V184 to 276V192 to 288V80 kVA
S25±25%165 to 275V173 to 288V180 to 300V60 kVA
S30±30%154 to 286V161 to 299V168 to 312V40 kVA

SELECT | Required Power Rating:

Power Rating (kVA)Max Rating (Amps per Phase)SVS-L-2P-S* Model No
(S*
=Select Swing Option Required)
220/110V230/115V240/120V
5 kVA22.7A / 2 x 22.7A21.7A / 2 x 21.7A20.8A / 2 x 20.8ASVS-5L-2P-S15~S30
10 kVA45.5A / 2 x 45.5A43.5A / 2 x 43.5A41.7A / 2 x 41.7ASVS-10L-2P-S15~S30
15 kVA68A / 2 x 68A65A / 2 x 65A62A / 2 x 62ASVS-15L-2P-S15~S30
20 kVA90A / 2 x 90A87A / 2 x 87A83A / 2 x 83ASVS-20L-2P-S15~S30
30 kVA136A / 2 x 136A130A / 2 x 130A125A / 2 x 125ASVS-30L-2P-S15~S30
40 kVA181A / 2 x 181A173A / 2 x 173A166A / 2 x 166ASVS-40L-2P-S15~S30
50 kVA227A / 2 x 227A217A / 2 x 217A208A / 2 x 208ASVS-50L-2P-S15~S25
60 kVA272A / 2 x 272A260A / 2 x 260A250A / 2 x 250ASVS-60L-2P-S15~S25
75 kVA340A / 2 x 340A326A / 2 x 326A312A / 2 x 312ASVS-75L-2P-S15~S20
80 kVA363A / 2 x 363A347A / 2 x 347A333A / 2 x 333ASVS-80L-2P-S15~S20
100 kVA454A / 2 x 454A434A / 2 x 434A416A / 2 x 416ASVS-100L-2P-S15
120 kVA545A / 2 x 545A521A / 2 x 521A500A / 2 x 500ASVS-120L-2P-S15
150 kVA681A / 2 x 681A652A / 2 x 652A625A / 2 x 625ASVS-150L-2P-S15

Note: All SVS-L-2P-S15~S30 Stabilisers are designed to support the full load at minimum input volts and maximum ambient temperature.

General Technical Specification

General:
 – Design Topology:Servo Electronic – Variable Transformer controlled
 – Phase:Two-Phase, 2 Wire (2P+G/E)
 – Power Ratings:11 Model Ratings-
5kVA, 10kVA, 15kVA, 20kVA, 30kVA, 40kVA, 50kVA, 60kVA, 75kVA, 80kVA & 100kVA
 – Frequency:50 / 60Hz (47 to 63Hz)
 – Power Factor:The Power Factor has no effect on performance providing the stabilizer is being used within its rated capacity
Input:
 – Nominal Voltage:220V -230V – 240V, Two-Phase, 2 Wire
 – Input Voltage Window Options (S*):S15Nominal Voltage ±15% (up to 100KVA)
 S20Nominal Voltage ±20% (up to 80KVA)
 S25Nominal Voltage ±25% (up to 60KVA)
 S30Nominal Voltage ±30% (up to 40KVA)
Output:
 – Voltage:220/110V -230/115V – 240/120V, Single Phase, 3 Wire (Customer to Specify)
 – Voltage Accuracy:±1% (Default) – adjustable ±1% to ±5%
 – Correction Time:Typically a 10% supply variation will be corrected to within 2.5% in 0.6 seconds
 – Efficiency:≥98%
– Overload Ratings:150% max. current rating for 10 seconds
Display Panel – Metering, Alerts & Communication:
 – Front Display Panel:Digital Metering:Output Volts, and Load
 Status Indication:On, Output Over and Under Volts & Output Normal & SPD Fault
Protection Features:
 – Surge Protection:TVSS – Protects loads against high-energy Spikes and Transient Voltages
 – Lightning Surge Protection:Class II SPD – protection against extremely high voltage surges and transients caused by lightning strikes on the utility mains supply line
 – Input Breaker:Standard on all models – delivers over current input protection
 – Bypass:Inbuilt Bypass Switch enabling the bypassing of the electronic controls circuitry to provide power direct to the load
 – Output Isolation:Automatic disconnection of the load in the event of a fault condition is detected
Environmental:
 – Operating Temperature Range:-15°C to +45°C
Derate by 2% for each additional °C up to max 60°C
 – Maximum Altitude:1000 meters (derate by 2.5% per additional 500 meters)
 – Relative Humidity:Suitable for indoor tropical use – 0 to 95% (non-condensing)
 – Harmonic Distortion:None introduced
 – Audible Noise:@ 1 meter 50 to 65 dBA (dependent on model rating)
Physical:
 – Power Connections:Hardwire Input & Output
 – Construction:Enclosures to IP20 / NEMA 1 Style – BS EN 60529  (Option – Outdoor IP54/NEMA 3 Style)
 – Paint Colour:RAL 7032 (Pebble Grey – Epoxy Powder Coating) – Other paint colours on specific request
 – Dimensions & Weights:Dependent on model rating and configuration
Sizes and weights available on individual request
Certification & Conformance:
 – EMC Conformance:BS EN 55022 and relevant parts of BS EN 61000
 – CE Certification:CE Marked – 2014/30/EU (The EMC Directive) and 2014/35/EU (The Low Voltage Directive)
 – Warranty:3 Years / 36 Months from date of supply
Optional Add-Ons:
 – Outdoor IP54 Enclosure (-IP54)Stabiliser presented in endurable IP54 (BS / EN 60529) / NEMA 3 free-standing steel cubicles suitable for external use, or more challenging internal environments
 – Input Isolating Transformer (-PC)Through the integration of a shielded isolation transformer, provides enhanced spike & electrical noise (Common Mode: 120db @ 100khz & Normal Mode Noise: 60db @ 100khz) suppression and neutral ground bonding. Delivers what is commonly referred to as a ‘CLEAN’ supply
 – Full Manual Maintenance Bypass (-MBS)An integrated/inbuilt traditional ‘Break Before Make’ bypass facility. Handy when performing remedial works, or deep maintenance on the system.
 – AquaStop (-AS)PCB protective coating offering protection against damp and moisture ingress
 – Digital Power Metering (-DPM)Output Digital Power Metering for monitoring V, A, W, VAR, PF, W Hrs & VAR Hrs and offering  RS-485 interface and event logging
 – Alternative Paint Colour (-RAL)Alternative Paint Colour Finish – customer to specify
 – Output Circuit Breaker (-OCB)Replacement of the Output Contactor with an Output Circuit Breaker
– UL Recognised Components (-URC)For applications where UL compliance is required, the Stabilizer / Conditioner can be supplied with UL approved Input Breakers and Output Contactors / Breakers, so that the client can obtain on-site UL approval of the installation

Note:
All SVS Stabilisers are designed to support the full load at minimum input volts and maximum ambient temperature.

Sales & Support

Data Sheet

– L Series [220/110V, 230/115V, or 240/120V Models]

Guide Specification

Operator / User Manual

Please contact us to request a copy of the Manual

CE Certification

SVS Series Split-Single Phase Servo Electronic AC Voltage Stabilisers / Conditioners comply with the relevant European Union (EU) health, safety and environmental protection directives and regulations and are duly CE marked.

Sinalda Declaration

EMC Directive – 2014/30/EU – in force from April 2016

Low Voltage Directive – 2014/35/EU – in force from April 2016

Independent 3rd party verification certificate

EMC Directive – 2014/30/EU – in force from April 2016

Low Voltage Directive – 2014/35/EU – in force from April 2016

If you do not find the Voltage Stabiliser or Power Line Conditioner that meets your application’s exact needs, please contact us with your specific detailed requirements.